Skip to product information
1 of 1

General Electric

GE LP33 Series 100kVA/90kW 208/120V In/Out Single Input Base Unit UPS

GE LP33 Series 100kVA/90kW 208/120V In/Out Single Input Base Unit UPS

Regular price $ 35,499.99 USD
Regular price $ 49,712.00 USD Sale price $ 35,499.99 USD
Sale Sold out
GE LP33 Series 100kVA/90kW 208/120V In/Out Single Input Base Unit UPS
 
Single Input. 3-Phase, 4-Wire + Gnd. For use with External Battery Cabinets - External Battery Cabinets Sold Separately. 
 
Part Number: UPS310LP2241100
 
Dimensions: 40 x 36 x 75"

The GE LP 33 Series is a highly reliable and cost effective three phase UPS system providing critical power protection for a wide range of applications. The LP 33 system operates in VFI mode (Voltage Frequency Independent) yielding the maximum levels of power reliability for all mission-critical processes. The GE LP 33 was developed using GE's Design for Six Sigma methodology to ensure that the product fully meets customer requirements and expectations.

The unit is equipped with a redundant power supply ensuring the load being transferred in an instant to the static bypass in the event of a breakdown of the power electronics. To further increase system reliability, 2 or more units can be connected in parallel using GE's unique redundant parallel architecture(RPA). In this way a redundant fault tolerant system is created with maximum availability and reliability. The decentralized bypass offers maximum flexibility to the end-user for future expansion of the system.

 

Through their complete life cycle, all GE UPS systems are fully supported by service teams which provide world-class, 24x7 preventive and corrective services, training and application expertise.

Features and Benefits

  • GE's unique booster-technology provides a high input power factor (0.98) and low input current harmonic distortion. The low input current harmonic distortion is constant for al load situations from 20% to 100% load.
  • Big savings can be achieved on energy costs due to the very high efficiency of this UPS system: 93%, on ECO Mode up to 98.6%.
  • Input/Output terminals are easily accessible from the front, as well as all other serviceable parts. Full front access provides the possibility to place the unit against a wall or in a "back to back" configuration, saving floor space.
  • EMC filters are standard installed in the UPS making sure that the system complies also with the future standards on emission of radio frequencies. The LP 33 Series complies with EN 62040 Class A ensuring compatibility in any environment.
  • The footprint of the LP 33 Series is compact. Combined with low weight it can be placed on any floor. The small footprint provides you with more space for other equipment.

Specifications

  • on-line double conversion topology
  • true sine wave output
  • > 3:1 Crest Factor
  • up to 93.3% efficiency in double conversion mode
  • up to 98.6% efficiency in ECO mode
  • parallel up to 4 units in RPA
  • CE listed

Product Scope

    • 3-phase in/out, 10-20-30-40-60-80-100-120 kVA
    • IGBT rectifier and inverter
    • 380/400/415V input voltage
    • 45-66Hz input frequency range
    • 380/400/415V input voltage
    • 50/60Hz output frequency (user selectable)

    MODEL

    LP33-10-UL

    LP33-20-UL

    LP33-30-UL

    LP33-40-UL

    LP33-50-UL

    LP33-60-UL

    LP33-80-UL

    LP33-100-UL

    Power Rating

    Output Capacity

    10kVA / 8kW

    20kVA / 16kW

    30kVA / 24kW

    40kVA / 32kW

    50kVA / 45kW

    60kVA / 54kW

    80kVA / 72kW

    100kVA / 90kW

    Power Factor

    Output Power Factor

    0.8

    0.9

    Energy Efficiency

    Double Conversion

    Up to 90%

    Eco Mode

    Up to 98%

    Physical

    Weight w/o batteries (lbs)

    397

    430

    772

    816

    1015

    1323

    Dims ( W x D x H ) (inches) (UPS only)

    22.7" x 30.7" x 51.6"

    23.6" x 29.6" x 71.7"

    28.4" x 28.5" x 71.7"

    39.4" x 35.4" x 75.0"

    Input

    Input Voltage

    3 x 208V + N

    Voltage Range

    -25% / +20%

    -20% / +15%

    -15% / +10%

    Frequency

    60 Hz +/- 10%

    Input THD

    < 8%

    < 10%

    Input Power Factor

    > 0.98 lagging

    Output

    Output Voltage

    120Y / 208 V

    Frequency

    60 Hz (+/- 1%)

    Crest Factor

    > 3:1

    Voltage Regulation

     

    – Static

    +/- 1%

    – 100% Step Load

    +/- 1%

    +/- 2%

    Voltage Distortion

     

    – 100% Linear Load

    < 2% THD

    < 1.5% THD

    < 2% THD

    – 100% Non-Linear Load

    < 3% THD (EN 50091)

    Overload Capability

     

    – Inverter

    125% for 10 minutes; 150% for 1 minute

    – Bypass

    200% for 2 minutes; 2000% for ½ cycle

    Battery

    Battery Type

    Valve Regulated Lead Acid (VRLA)

    Float Voltage

    328 VDC @ 68° F (20° C)

    Min Discharge Voltage

    236 VDC (programmable)

    General

    Audible Noise db(A)

    50

    55

    61

    62

    65

    65

    68

    Operating Temperature

    UPS: 32° to 104° F (0° - 40° C); Battery: 68° to 77° F (20° - 25° C) recommended

    Humidity

    0-95%; non-condensing

    Safety Classifications & Listings

    UL/cUL : UL 1778 / IEC62040 / ISO 9001

    EMI Classification

    FCC Part 15, Class A, IEC 62040-2 Class A

    Surge Protection

    IEEE 587-B / ANSI C62.41-B / IEC 1000-4

    Communication / Connectivity

    RS-232; programmable alarm contacts; open collector outputs; SNMP (optional)

    Color

    White (RAL 9003)

    Warranty

    Twelve (12) months after commissioning or eighteen (18) months after shipment, whichever occurs first *

    View full details