2015 Surplus New Eaton PW 9155-10kVA 9kW 32 Battery UPS

Regular price
$ 7,311.75
Sale price
$ 7,311.75
Regular price
$ 12,227.00
Sold out
Unit price
Quantity must be 1 or more

Surplus New - 2015 Model

The Eaton 9155 is a Double-Conversion Online, Split-Phase UPS and requires a hardwired input connection of 200-240VAC with Neutral or with Optional Input Transformer Module. The optional input transformer module is used to provide a neutral connection for the UPS input when none exists in present building wiring. Output Voltage is 100/200, 110/220, 120/240 with 180° phase displacement or 120/208, 127/220 with 120° phase displacement.

General
Topology Double-conversion
Catalog Number K41011000000000
Part Number K41011000000000
Color Black
Rating (VA/Watts) 10000/9000
Diagnostics Full system self-test at startup
UPS Bypass Automatic on overload or UPS failure
Dimensions (H x W x D, inches) 32.2 x 12 x 33.7
Weight (lbs) 352
Warranty Two-year factory warranty
Contents
(Ships with the following items)
1 ready-to-go UPS
Software Suite CD
User Guide
Efficiency 92% with nominal linear load; 91% with nominal computer load.
Electrical Input
Connection
Hardwired - see manual for terminal block layout
Frequency 50/60 Hz (45 to 65 Hz)
Frequency Range 45 to 65 Hz
Input Power Factor P.F >0.99 typical, >0.96 frequency converter
Generator Compatability Yes
Electrical Output
100/200, 110/220, 120/240 Vac 180° phase displacement; 120/208, 127/220 Vac 120° phase displacement
Output Receptacles
(1) PDM
On Utility Voltage Regulation Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change
On Battery Voltage Regulation Output voltage regulation ±1% Static; ±5% dynamic at 100% resistive load change
Overload Capacity 150% for 5 sec / 125% for 1 min (online), 110% for 10 min
Voltage Wave Shape (On Battery) Sine Wave
Transfer Time 0 ms
Battery
Battery Type 9Ah, sealed, lead-acid, maintenance-free
Battery Replacement Field-replaceable
Start On Battery Allows start of UPS without utility input
Recharge Time Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage after full load discharge External battery: no more than 10x discharge time to 90% usable capacity at nominal line voltage after full load discharge
Communications
User Interface LCD Display with blue backlight
LEDs (4) LEDs for notice and alarm
Audible Alarms Yes
Communication Ports (1) RS-232, (1) relay contact, (1) REPO, (2) environmental input
Communications Slot (2) X-Slot communication bays
Power Management Software Bundled Software Suite CD
Environmental & Standards
Audible Noise <53dBA at 1 meter (noise less room) typical
Operating Temperature 10°C to +40°C, +45°C with 7.5% derating; Batteries recommended max. +25�C
Markings UL, cUL, CSA, CE and NOM-NYCE
Storage Temperature -15°C to +25°C
Relative Humidity 0-95%, non condensing
Go to full site